Model: DM-III Multitest
F
Advanced Digital Power Quality Recorder / Datalogger
|
|
Amprobe’s full-featured Three-Phase Power Quality Recorders provide
the essential functions and capabilities required to operate
accurately and effectively in today’s demanding electrical
environments.
Features:
POWER QUALITY ANALYZER/ DATA LOGGER:
- True RMS (TRMS)
- Measures and Records Broad Spectrum of Power Quality
Parameters: AC Current, AC Voltage to 600V including Sags and
Surges, Harmonics (THD and individual up to 49th), Active,
Reactive and Apparent Power & Energy, Peak Demand, Power Factor,
Frequency measurement, Phase sequence
- Compatible with wide range of Current Transducers
DM-CT-100: 0.5A to 100A
DM-CT-HTA: 5 - 1000A (Supplied with DM-III
Multitest)
AM-Flex33: SElectable: 5 - 1000A or 15 - 3000A (Supplied with DM-III
Multitest F)
- Comes as a complete kit: CTs, Voltage Leads, Ground
Probes & Leads, PC software and download cable are included with
this product.
- Works with single and three phase systems (Y and Delta)
- Detects and records voltage anomalies, Sags and Surges
- Built in scope displays waveforms
- Phase sequence indication
- Records up to 64 parameters (single or three phase)
simultaneously
- Manual
and programmable recording start
- Password protection
- Selectable fundamental frequency of 50 or 60 Hz
- Special data compression system and user selectable rates
allow recording from several hours to several years
- Download capabilities, Windows compatible PC software
- Displacement power factor for power factor correction
determination
- Line or battery powered
- Safety: CATIII, 600V Phase to phase, CATIII, 300V Phase to ground, EN
61010-1+A2(1996)
MEGOHMMETER FUNCTIONS:
- Tests insulation of wires,
cables, transformers and electrical motors
- Selectable test voltages up to 1000V
- Programmable timer to perform the Dielectric Absorption Ratio
Test
- Sensitive Ohmmeter for checking resistance of motor windings
- Selectable polarization of ohmmeter for checking grounding
continuity
- Automatic voltmeter protects against misuse on hazardous
energized systems
GROUND RESISTANCE & RESISTIVITY FUNCTIONS:
- Three measuring
modes;
a) 2 point continuity/resistance test
b) 3 point Fall of Potential test
c) 4 point Earth Resistivity measurement
- Automatic voltage measurement prevents false measurements
- Automatically applies three testing frequencies for the most
accurate readings
-
Accumulates the average of multiple tests and displays the
individual test results and the number of tests.
- Detects faulty test conditions such as poor soil conditions and
noise at the inputs.
PHASE SEQUENCE
- Phase sequence indication
- Frequency measurement
- Phase – to – Phase voltage measurement.
Spec
Sheet (PDF file)
|
Specifications: |
|
Supplied Current Transducer: |
AM-FLEX33 3000A
Flexible 7” internal diameter
CT +/- (0.5% Rdg
+ 2 LSD |
|
AC Current : |
DM-CT-100:
(optional) 0.5A to 100A
DM-CT-HTA:
(optional) 5 - 1000A
AM-FLEX33: Selectable: 5 – 1000A or 15 - 3000A +/-
(0.5% Rdg + 2 LSD) |
|
AC Voltage including Sags and Surges: |
0 - 600V
+/- (0.5% Rdg + 2 LSD) |
|
Harmonics: |
THD, DC
and individual up to 49th +/- (0.5% Rdg + 2 LSD) |
|
Power: |
Working
(W), Reactive (VAR) and Apparent (VA) +/- (1.0% Rdg + 2 LSD) |
|
Energy: |
Working
(kWh), Reactive (VARh) and Apparent (VAh) +/- (1.0% Rdg + 2
LSD) |
|
Peak Demand: |
KW +/-
(1.0% Rdg + 2 LSD) |
|
Power Factor: |
0.00 –
1.00 |
|
Frequency measurement: |
57 to
63.6 Hz at 60Hz fundamental 47 to 53 Hz at 50Hz fundamental
+/- (1.0% Rdg + 2 LSD) |
|
Phase sequence: |
1 - 2 - 3 |
|
Co-generation: |
Computes
incoming and outgoing energy |
|
Frequencies: |
50/60 Hz |
|
Available Recording Time: |
Several
hours to several years depending on setup |
|
Insulation resistance with 50 VDC test
voltage: |
0.01-19.99, 49.9 +/- (2% Reading + 2 digits) 49.9 - 99.9MΩ
+/- (5% Reading + 2 digits) |
|
Insulation resistance with 100 VDC test
voltage: |
0.01-19.99, 99.9 +/- (2% Reading + 2 digits) 99.9 - 199.9MΩ
+/- (5% Reading + 2 digits) |
|
Insulation resistance with 250 VDC test
voltage: |
0.01-19.99, 199.9, 249 +/- (2% Reading + 2 digits) 249 -
499MΩ +/- (5% Reading + 2 digits) |
|
Insulation resistance with 500 VDC test
voltage: |
0.01-19.99, 199.9, 499 +/- (2% Reading + 2 digits) 499 -
999 MΩ +/- (5% Reading + 2 digits) |
|
Insulation resistance with 1000 VDC test
voltage: |
0.01-19.99, 199.9, 999 +/- (2% Reading + 2 digits) 999 -
1999 MΩ +/- (5% Reading + 2 digits) |
|
Low resistance (without timer): |
0.01-19.99, 99.9Ω +/- (2% Reading + 2 digits) |
|
Low resistance (with timer): |
0.01-9.9Ω
+/- (2% Reading + 2 digits) |
|
Ground resistance: |
0-19.99,
199.9, 1999 Ω +/- (5% Reading + 3 digits) |
|
Ground resistivity: |
0.6-
125.6 Ωm 0.125-1.256, 19.99, 199.9 kΩm +/- (5% Reading
+ 3 digits) |
Related: Amprobe DM-III
Multitest -
Power Quality Recorder |
|
Ordering Information: |
|
|
AM-DM-III-Multitest-F |
Digital
Power Quality Recorder |
|
Optional Accessories: |
|
|
AM-DM-CT-100 |
100A Compact Current Transducer (0.5A to 100A)
 |
|
|
AM-DM-CT-HTA |
1000A
Current Transducer (supplied with the DM-III
Multitest) |
|
|
AM-CC-DM-III |
Optional
Hard Case for the DM-III Multitest and DM-III Multitest F (meter
not included) |
|
|
RC-AM-RS-USB |
USB
to RS-232 Adapter |
|
|
|

Power
Quality
Power Quality
Recorders Compared
|